DHTML Menu, (c)2004 Apycom

Techna International Ltd., Peace of Mind With Power

  site map          
 

TR11 Thermal Breaker

The Techna TR11 Circuit Breaker for equipment, is a single pole push-to-reset, thermally operated overload protector, providing reliable, trip-free operation on overloads and short circuits, within the maximum breaking capacity specified. The latching trip mechanism maintains high contact force preventing contact bounce and reducing the risk of contact welding.

The TR11 is a drop-in replacement to the ETA 1140 series circuit breaker.


Typical applications
Main applications are the protection of single phase motors, transformers, UPS, power strips, solenoids, etc., against damage due to over-current conditions.


Operation
The mechanism of the circuit breaker is designed to open the contacts in the event of a current flow in excess of the rated current according to the time/current characteristics of the device. A bimetal strip, which has the advantage of being immune to high inrush currents and line transients is heated by an over-current and deflects, thereby releasing the latch mechanism. The contacts open even if the reset button is manually held in the closed position. This is known as a trip free mechanism. The contacts open and close with a positive snap action and the tripped state is clearly indicated by the white band visible on the extended projection of the reset button.


Auxiliary Terminal
The circuit breaker can be supplied with an auxiliary terminal input - this provides the ability to connect a non protected auxiliary circuit to the breaker for signalling purposes.


Download more information on TR11 Thermal Circuit Breakers (PDF 286KB)

 
Techna TR11 thermal circuit breaker
 
    techna tr11 thermal breakers have VDE certification   techna tr11 thermal breakers have CSA certification  
    techna tr11 thermal breakers have UR certification      

Technical Data

Current ratings (A) 0.5, 0.9, 1.0, 1.2, 1.5, 1.8, 2, 2.2, 2.5, 2.7, 3, 3.3, 4, 5, 6, 6.5, 7, 8, 9, 10, 12 and 16
Rated voltage (V) 240Vac 50/60Hz; 32V DC/24V DC (VDE)
Initial insulation resistance > 100W
Di-electric strength 1.5 KV for one minute
Overload switching capacity 6x In~, 4x In–
Maximum breaking capacity 8x In for <6A ac, 6x In or 60A dc (whichever is higher) for ³6A
Conditional short circuit current 1000 A PC1 category
Power loss 1 - 2 Watts
Interrupting capacity (UL1077) 1000A, 240VAC, 32VDC
Operating temperature Max. 60ºC ambient
Operational life at 2 x In 1000 cycles
Limited short circuit current 1000 Amps PC 1
Degree of protection IP 40 for Accessible Range ; IP 00 for Termination range
Standards IEC 60934, CSA 22.2 No. 235, UL-1077
Weight 10g (without nut)

UL/CSA Ratings

Current rating (A) 0.5 to 16A
Voltage rating (V) 240Vac / 32Vdc

VDE Ratings

Current rating (A) 0.5 to 16A
Voltage rating (V) 240Vac / 24Vdc
    techna tr11 thermal breaker dimensions  
           
             
 
 

Also Available...

Circuit Protection Index
T74 Thermal Breaker
T16 Thermal Breaker
TR11 Thermal Breaker Part Numbers

 
 
 

Download...

Download TR11 PDF (286KB)