DHTML Menu, (c)2004 Apycom

Techna International Ltd., Peace of Mind With Power

  site map  
 

Residual Current Devices, RCDs & RCBOs
(Earth Leak/Ground Faults) (GFCIs)

Our range of RCCBs and RCBOs provide all the options you need for complete protection against earth leakage and residual current faults and additionally offer combined earth leak and overload protection in RTEC and SmartGuard ranges.

The RCD range (CTEC) from Techna offers both 2 and 4 pole devices in 30mA - 500mA trip sensitivities, with main current ratings of 25A, 40A, 63A and 100A.

The RCD protects against residual currents (earth leaks/ground faults), where a small current may leak from the circuit due to bad insulation. Critically the residual current device will react to leakage currents as low as 30mA. This is an essential protection requirement as earth leaks at these low currents are too small to trip a conventional circuit breaker, but still large enough to cause fatal electric shock and/or start fires due to arcing. The sensitivity of the RCD is defined by its mA rating. The main current rating of the device denotes only the maximum current the RCD can carry and does not affect the protection characteristics. So, for example, if you required a 25A/30mA RCD, you could also use a 40A/30mA or 63A/30mA. However, the lower current device (25A) costs less as the lower rated contact mechanism is less expensive to produce.

The RTEC RCBO protects against residual currents (earth leaks) and short circuits (overloads). An RCBO can be used where a single device is needed to provide both earth leak and overload protection, perhaps because the circuit is not fed from an RCD protected branch. This is useful for wiring spurs and pieces of equipment that could also benefit from space saved by using the single RCBO device (as opposed to a separate MCB and RCD). As the short circuit sensing is only on the live pole, it is essential that live and neutral are wired correctly to the RCBO as indicated on the front of the device.

Due to the additional overload feature of our RTEC RCBO, when ordering, the main current rating must also be specified to match the main current rating of your circuit.

 
Techna CTEC residual current circuit breaker (RCCB)
 
   
Techna RTEC residual current circuit breaker with overload (RCBO)
 
 
Techna CTEC residual current circuit breakers (RCCBs) CTEC Series
Residual Current Circuit Breakers (RCCBs)techna semko standard
techna rtec residual current circuit breaker; rcbo  RTEC Series
Residual Current Circuit Breakers with Overload (RCBOs)techna tuv standard
Techna SmartGuard residual current circuit breaker with overload PD Series (SmartGuard)
Residual Current Circuit Breakers with Overload

Handle actuator; front panel or Din rail mounting; equipment ground fault protection; 1-3 poles; switched or unswitched neutral options; 1-50 amps, up to 480Y/277VAC; 7-100 milliamp equipment leakage trip current; LED leakage trip indicator; UL, CSA

techna UL standard

 
 
         
 
 

Also Available...

Circuit Protection Index
Electrical Products Index
RCD Part Numbers